Development of insulation moisture level criteria as a result of technological progress in the maintenance system of oil-filled transformers
https://doi.org/10.24223/1999-5555-2022-15-4-253-262
Abstract
Transformers are critical elements of electrical networks and systems. The operational reliability of oil-filled transformers largely depends on the characteristics of the insulation, which is confirmed by the failure statistics. A number of factors affecting the insulation of electrical machines are identified, including excessive moisture, with its negative consequences outlined. The complexity and shortcomings of the use of traditional technologies for drying solid insulation are indicated, which focus on the search and implementation of the latest technologies in the system of maintenance and repair of transformers — automated insulation restoration systems (AIRS).
Taking into account the development of technical progress in the field of service maintenance of transformers, the negative impact of moisture on the reliability, durability and overload capacity of electrical machines, especially those beyond their normal service life, a new look at the criteria for the moisture content of cellulose insulation is proposed. A review is made of the normative requirements for the moisture content of the insulation of oil-filled transformers of a number of Russian and foreign standards. On the basis of the Oommen equilibrium curves, the shortcomings of the lack of comparability of the humidity criteria for solid and liquid insulation in STO 34.01–23.1– 001–2017 and RD 34.45–51.300–97 are presented. It is proposed to single out several areas of the operational state of transformers in terms of “moisture content of solid insulation (paper)”. The optimal period for the use of AIRS has been determined.
The AIRS technology is implemented in a TRANSEC module, which enables to carry out work under load, without adversely affecting predictive diagnostics. The design features of the TRANSEC module, the principle of operation, functional and design differences from standard transformer units – thermosiphon /adsorption filters — are outlined. The results of testing the TRANSEC technology in an existing electrical installation serviced by PJSC Rosseti are presented. Six months of trial operation of the TRANSEC module demonstrated the restoration of insulation characteristics on operating equipment without additional involvement of personnel. Besides, during the testing of the TRANSEC technology, the influence of oil temperature on the information content of the assessment of solid insulation parameters was confirmed. Proposals are formulated on the revision of industry documentation in the established part.
About the Authors
S. P. VysogoretsRussian Federation
17 N, Nevsky Prospect, 147, St. Petersburg, 191024
D. M. Nesterenko
Russian Federation
University street, 4, HMAO-UGRA, Surgut, 628408
V. V. Lopatin
Russian Federation
University street, 4, HMAO-UGRA, Surgut, 628408
S. M. Redkin
Russian Federation
17 N, Nevsky Prospect, 147, St. Petersburg, 191024
References
1. Vysogorets S. P. Improving the methodology of physical and chemical diagnostics of oil-filled transformer equipment: dis. … Dr. tech. Sciences: 05.14.12. – St. Petersburg 2020,: 423.
2. Przybylek P. Application of Synthetic Ester for Drying Distribution Transformer Insulation – The Influence of Cellulose Thickness on Drying Efficiency / P. Przybylek, H. Moranda, H. Moscicka-Grzesiak, D. Szczesniak // Energies 2019, 12,: 3874.
3. Arroyo O. Aging characterization of electrical insulation papers impregnated with synthetic ester and mineral oil: Correlations between mechanical properties, depolymerization and some chemical markers / O. Arroyo, I. Fofana, J. Jalbert, S. Gagnon, E. Rodriguez-Celis, S. Duchesne, M. Ryadi // IEEE Trans. Dielectr. Electr. Insul. 2018, 25 (1).: 217–227.
4. STO 34.01-23.1-001-2017 The scope and norms of electrical equipment tests. Approved by the order of PJSC “Rosseti” dated 26.05.2017 No. 280r “On approval of the organization standard”, Moscow. 241.
5. Methods for assessing the technical condition of the main process equipment and power lines of power plants and electrical networks. Order of the Ministry of Energy of the Russian Federation dated July 26, 2017 No. 676. [electronic resource]. Professional reference systems "TechExpert" http://docs.cntd.ru/document/456088008 (date of the application: 06.10.2022).
6. RD 34.45–51.300–97. Scope and standards of electrical equipment testing / Under the total. ed. B. A. Alekseev, F. L. Kogan, L. G. Mamikonyants – 6th ed., rev. and additional – M.: ENAS 2007.: 256.
7. Ageing of cellulose in mineral oil insulated transformers / CIGRE D1_01_10. – Brochure 323: 2017.
8. Order of the Ministry of Energy of the Russian Federation of February 8, 2019 N 81 "Requirements for the overload capacity of transformers and autotransformers installed at electric power facilities", as amended on December 28, 2020 [electronic resource] // Consortium KODEKS https://docs.cntd.ru/document/542642849 (accessed 06.10.2022).
9. Vysogorets S. P., Redkin S. M., Zhitenev M. V. Search for modern engineering solutions for automatic control of the technical condition of transformer insulation // Materials Science. Energy 2021, (27) 3.: 50–62. DOI: 10.18721/JEST.27305.
10. IEC 60422:2013. Mineral insulating oils in electrical equipment. Supervision and maintenance guidance // International electrotechnical commission. ICS 29.040.10. ISBN 978-2-83220-560-0.: 18.
11. IEEE 62–1995. IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus – Part 1: Oil Filled Power Transformers, Regulators, and Reactor. 01 December 1995. ISBN: 978-0-7381-0831-5. DOI: 10.1109/IEESTD.1995.122640.:64.
12. Notice No. 1. On amendments and additions to the «Scope and standards for testing electrical equipment: SO 34.45–51.300–97 (RD 34.45–51.300–97) 6th edition with amendments and additions as of 01.03.2001» [electronic resource] // RuFOX LAWS https://law.rufox.ru/view/14/1200045580.htm (accessed 08/31/2022).
Review
For citations:
Vysogorets S.P., Nesterenko D.M., Lopatin V.V., Redkin S.M. Development of insulation moisture level criteria as a result of technological progress in the maintenance system of oil-filled transformers. Safety and Reliability of Power Industry. 2022;15(4):253-262. (In Russ.) https://doi.org/10.24223/1999-5555-2022-15-4-253-262