Analysis of reliable and safe heat supply of residential buildings using waste water after DHW heat exchangers
https://doi.org/10.24223/1999-5555-2020-13-1-41-47
Abstract
A modified scheme of heat supply of residential buildings with dependent connection to external heating networks, providing reliability of heat supply and the necessary comfort in the premises due to mixing of waste water after domestic hot water (DHW) heaters at an outdoor temperature exceeding the temperature graph break point, is considered. A review of possible ways to improve the reliability and safety of heat supply, improve the efficiency of heat sources, as well as regulate heat supply and prevent "overheating" near the beginning and end of the heating period is carried out. Calculations are carried out to determine the actual amplitude of temperature fluctuations in residential buildings with a daily variation in water flow rate after hot water heaters in the conditions of application of the considered scheme of connecting buildings to the heating network. Analysis of obtained results is given, and conclusions are drawn concerning the expediency of application of the above scheme. It is established that, given the thermal stability of enclosing structures, the daily flow rate fluctuations have no significant effect on the stability of the temperature regime of residential buildings and the comfort of their indoor microclimate at high outdoor air temperatures. It is shown that, in terms of reliability of heat supply of the main group of residential buildings and ensuring the life safety, the offered scheme is not inferior to the standard two-stage scheme of connection of DHW heat exchangers, with restriction of the total consumption of network water and with dependent control of heat supply to DHW, heating and ventilation. It is noted that in the scheme under consideration, the daily average consumption of network water to domestic hot water heaters over most of the heating period is higher or equal to the estimated consumption for heating and ventilation systems, which minimizes the time of using the mixing pump and provides for the regulation of heat supply only at the expense of the wastewater circuit.
Keywords
About the Author
O. D. SamarinRussian Federation
Yaroslavskoye Highway, 26, 129337, Moscow.
References
1. Rotov P. V., Orlov M. E., Sharapov V. I., Sivukhin A. A. The increase of efficiency of operation of centralized heat supply systems by using heat pump units. Industrial power-engineering 2014; (7): 27 - 31. (In Russ.)
2. Sharapov V. I. On some aspects of the technical policy in the heat supply. Energy saving and water treatment 2013; (5): 9 - 12. (In Russ.)
3. I. E.Goloborod'ko, S. A. Kozlov, A. N. Gudko. Discussion: sweating boilers and low-temperature schedule in heating systems. Sanitary engineering. Heating. Air conditioning 2016; (1): 26 - 30. (In Russ.)
4. Gavey O. F., Panferov V. I. The development of control algorithms for heat supply systems with the heat transfer agent temperature changes. Proceedings of the VI International Science and Technical Conference «Theoretical foundations of heat and gas supply and ventilation». - Moscow : NR MSUCE 2015; 264 - 268. (In Russ.)
5. Rafalskaya T. A. Reliability and controllability of systems of centralized heat supply // Eastern European Scientific Journal 2016; (2): 228 - 235.
6. De Rosa M., Bianco V., Scarpa F., Tagliafico L. A. Modelling of en¬ergy consumption in buildings: an assessment of static and dynamic models. Russian Journal of Construction Science and Technology 2016; 1(2): 12 - 24.
7. Paiho S., Abdurafikov R., Hoang H. Cost analyses of energy-efficient renovations of a Moscow residential district. Sustainable Cities and Society 2015; 1(14): 5 - 15.
8. Samarin O. D. The secure and safe heat supply of residential buildings during the transitive climatic conditions. Safety and Reliability of Power Industry 2018; 2(11): 149 - 153. (In Russ.)
9. Samarin O. D. The secure and safe heat supply of residential buildings using the waste water after the heat exchangers for hot water supply. Safety and Reliability of Power Industry 2019; 2(12): 120 - 125. (In Russ.)
10. Khrustalev B. M., Kuvshinov Yu. Ya., Kopko V. M. Heat supply and ventilation. The 3rd ed., rev. and suppl. Moscow: ASV Publishers 2010; 784. (in Russ.)
11. SP (Set of Rules) 131.13330.2012 «Actualized edition of SNiP (Building Code) 23-01-99* "Building climatology"». - Moscow: Minregion RF 2012; 109. (in Russ.)
12. SP (Set of Rules) 30.13330.2012 «Actualized edition of SNiP (Building Code) 2.04.01-85 "Domestic water supply and drainage systems in buildings"». - Moscow: Minregion RF 2012; 68.
13. SP (Set of Rules) 50.13330.2012 «Actualized edition of SNiP (Building Code) 23-02-2003 "Thermal performance of the buildings"». - Moscow: Minregion RF 2012; 96. (in Russ.)
14. Bogoslowsky V. N. Building thermal physics (the thermal physical foundations of heating, ventilation and air condition) - 3th ed. - St.-Petersbourg.: AVOK-Severo-Zapad Publishers 2006; 400. (in Russ.)
15. GOST (National Standard of Russian Federation) 30494-2011 «Residential and public buildings. Microclimate parameters for indoor enclosures». - Мoscow: Rosstandart; 2011; 11. (in Russ.)
16. Samarin O. D. The calculation of building cooling under emergency conditions to ensure their heating reliability. Proceedings of Moscow State University of Civil Engineering 2019; 4(14): 311 - 316. (in Russ.)
17. Building climatology. Reference book to SNiP (Buildings rules and regulations) 23-01-99*. Under ed. of Savin V. K. - Moscow: NIISF 2006; 258.
Review
For citations:
Samarin O.D. Analysis of reliable and safe heat supply of residential buildings using waste water after DHW heat exchangers. Safety and Reliability of Power Industry. 2020;13(1):41-47. (In Russ.) https://doi.org/10.24223/1999-5555-2020-13-1-41-47