Improving reliability of porcelain post insulators at electric power Substations
https://doi.org/10.24223/1999-5555-2019-12-4-286-289
Abstract
At electric power substations, post insulators are designed for isolation and fastening of conductive parts of electrical installations. Insulators are installed on outdoor switchgear of substations as part of the main switching equipment. During operation, they are exposed to external atmospheric effects, mechanical and dynamic loads. Timely replacement of post insulators increases significantly the reliability of the main substation equipment at power substations. The question of improving reliability at transformer and traction substations is considered, external and internal factors associated with destruction of porcelain post insulators (PPI) are presented. It is established that the main cause of damage to PPI are sharp changes in ambient temperature, especially the transition of temperature values through 0°C. A model of a porcelain post insulator with an insulating body of elliptic shape is proposed. Operation of the proposed device is described. Analysis is presented of the ratio of the lengths of the axes of a circle and ellipse (major-to-minor) as related to spatial positioning in power loads. It has been determined by calculation that a post insulator should be installed in such a way that the major axis of the ellipse be aligned in the direction of the temperature gradient — sunlight, to reduce the impact of heating on the minor axis of the insulator.
About the Author
A. S. LukovenkoRussian Federation
Armeyskaya str., 31, 660005, Krasnoyarsk
References
1. Gaivoronsky A. S., Damage of composite insulators and their diagnosis during operation. Chief power 2010; (2): 23 – 27. (In Russ.)
2. Vorotnitsky V. E., Dmitriev I. N., Hammer A. V., Demin A. N. Diagnosis of the mechanical state of supporting-rod porcelain insulation of highvoltage disconnectors in operation. The energy of a single network 2014; 2(13): 4 – 14. (In Russ.)
3. Lukovenko A. S., Khristinich R. M. Improving the reliability of equipment electric power substations traction power supply when working in critical conditions. ELECTRO. Electrical engineering, electric power industry, electrical industry 2016; (2): 36 – 40. (In Russ.)
4. MES Siberia started to replace the core insulation at substations 220 – 1150 kV [Electronic resource] // Internet newspaper Newslab URL:http://newslab.ru/news/284791. (In Russ.)
5. GOST 20419-83. Ceramic electrotechnical materials. Classification and technical requirements. (In Russ.)
6. Galayko V. V., Lukovenko A. S. the Reference insulator. Patent No. 191692 (RU). Bulletin of inventions 2019; (23). (In Russ.)
Review
For citations:
Lukovenko A.S. Improving reliability of porcelain post insulators at electric power Substations. Safety and Reliability of Power Industry. 2019;12(4):286-289. (In Russ.) https://doi.org/10.24223/1999-5555-2019-12-4-286-289