Enhanced analytical model of power transmission line icing

https://doi.org/10.24223/1999-5555-2018-11-3-222-226

Abstract

Accidents in power transmission lines under icing conditions, in particular, those of cables, cause a great economic damage in Russia. Because of the lack of the possibility to forecast and evaluate reliably the consequences of weather conditions contributing to icing of transmisison line cables, power grid services often have to go to the place of a potential accident relying on guesswork. This leads to considerable losses of time and material resources, while the average recovery time of a damaged high voltage power transmission line is 5–10 days.

For the effective prediction and timely prevention of negative consequences of icing of on power line cables, an analytical model that describes the growth of ice on the surface of the electrical cable has been developed. The model is based on a widely applicable analytical model of [1], supplemented with dependence of the growth of ice sleeve on the angle between the wind direction and the cable, and on the electric field strength of the cable.

The results obtained using the new analytical model and the [1], model have been compared and show that as the angle between the wind direction and the cable decreases, the intensity of the ice growth decreases significantly. At the same time, the strength of the electric field of the cable affects negligibly the trajectory of water droplets.

A conclusion is drawn about insignificance of electrical field strength of the electric cable as a factor of growth of ice deposits. It is stated that the ice thickness value obtained using the developed model can be increased under specific weather conditions and design parameters of transmission lines. The obtained model can be improved by using other physical effects that affect icing of electric cables. Further, the model can be introduced in operation of energy companies to monitor the condition of power transmission lines and to carry out anti-icing activities.

About the Author

M. V. Timofeeva
Skoltech, CES
Russian Federation

Nobelya str., 3, 121205, Moscow



References

1. Goodwin E., Mozer J., Di Gioia A., Power B. Predicting ice and snow loads for transmission lines. In the Proceedings of the First IWAIS 1983; 1(1): 267–273. (In Eng.)

2. Institute Energosetproekt. Available form: https://aoesp.ru/ contacts. (In Russ.)

3. Guides of electrical equipment usage. 7th ed. St. Petersburg DEAN 2008. (In Russ.)

4. Lozowski E., Stallabrass J., Hearty P. The Icing of an Unheated, Nonrotating Cylinder. Part I: A Simulation Model. Journal of Climate and Applied Meteorology 1983; 22(12):2053–2062.

5. Ma H., Chen W., Zhang D. Numerical investigation of engine inlet vane hot–air anti–icing system with surface air film. International Journal of Modern Physics: Conference Series 2012; 19: 331–340. (In Eng.)

6. Lozowski E., Makkonen L. Fifty years of progress in modelling the accumulation of atmospheric ice on power network equipment. Proc. Eleventh International Workshop on Atmospheric Icing on Structures. Montreal 2005. (In Eng.)

7. Finstad K., Fikke S., Ervik M. A comprehensive deterministic model for transmission line icing applied to laboratory and field observations. In the Proceedings of the Fourth IWAIS 1988; 6(1): 227–231. (In Eng.)

8. Mitten P., Makkonen L., Morris R. Development of an operational ice and wind loading model for transmission lines. Canadian Electrical Association Conference. Montreal 1988; 15: 21–23. (In Eng.)

9. Farzaneh M. Ice accretions on high-voltage conductors and insulators and related phenomena. Philosophical Transactions of the Royal Society A: Mathematical, Physical and Engineering Sciences 2000; 358(1776): 2971–3005. (In Eng.)

10. Nikiforov E. Icing related problems, effect of line design and ice mapping. Special Rep. US Army Cold Regions Res. Eng. Lab.Hanover 1982; 82(26): 239–245. (In Eng.)

11. Butikov E., Bykov A., Kondrat’ev A. Physics in examples and problems. 4th ed. Ripol Classic 2015. (In Russ.)

12. Dyakov A. Electric networks of high voltage in Russia. Theoretical and practical basis. Energoprogress Corporation 2012. (In Russ.)

13. Regulations for electrical installation. Novosibirsk. Siberian university edition 2006. (In Russ.)


Review

For citations:


Timofeeva M.V. Enhanced analytical model of power transmission line icing. Safety and Reliability of Power Industry. 2018;11(3):222-226. (In Russ.) https://doi.org/10.24223/1999-5555-2018-11-3-222-226